Eaton 400A Fuse Holder, 3P-Pole for NH2 Fuse

Subtotal (1 unit)*

MYR4,422.08

Add to Basket
Select or type quantity
Stocked by manufacturer
  • Ready to ship from 06 July 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per Unit
1 +MYR4,422.08

*price indicative

RS Stock No.:
127-395
Mfr. Part No.:
183068 XNH2-FCL-S400-BT
Manufacturer:
Eaton
Find similar products by selecting one or more attributes.
Select all

Brand

Eaton

Product Type

Fuse Holder

Number of Poles

3

Body Material

Polyamide

IP Rating

IP10, IP20, IP2XC

Compatible Fuse Size

NH2 Fuse

Minimum Operating Temperature

-5°C

Maximum Operating Temperature

55°C

Standards/Approvals

IEC/EN 61439, RoHS

Terminal Type

Clamp

Series

xEffect

RoHS Status: Exempt

COO (Country of Origin):
DE

Eaton xEffect Series Fuse Holder, 400A Current, 800V Voltage - 183068 XNH2-FCL-S400-BT


This fuse holder is a three-pole device designed to house NH2 fuse-links for use on busbar systems within industrial switchgear. It provides front-access actuation and box Terminal connections for heavy-copper conductors, enabling straightforward installation in panel and busbar arrangements where Visual fuse monitoring is required.

Features & Benefits


• Rated for 400A continuous current for high-current circuits
• Insulation withstands up to 800V AC for elevated system voltages
• Conditioned short-circuit rating 120 kA for fault tolerance
• Sliding inspection windows enable safe voltage verification
• Box terminals accept 95 to 300mm² single lugs for large conductors
• IP20 protection in service with IP10/IP2XC states during maintenance

Applications


• Suitable for industrial panel distribution with NH2 fuse-links
• Ideal for integration into 60mm busbar systems in switchgear
• Used with heavy-current feeders in manufacturing plants
• Suitable for front-mounting where Visual fuse indication is needed

What conductor sizes can I terminate at the box terminal?


Single cable lugs from 95mm² up to 300mm² are supported, while stranded cable ranges include 25mm² to 240mm² depending on Terminal configuration.

How does the device indicate a blown fuse?


It provides optical signalling of triggered fuse-links so an operator can identify a blown fuse from the front.

Which mechanical mounting orientations are permitted?


It can be mounted vertically or horisontally on busbars with a 60mm spacing.

What are the operating temperature limits for installation?


The ambient operating range is −25 °C to 55 °C for normal service conditions.