Siemens, SIRIUS 3RU2 Thermal Overload Relay 1 NO/1 NC, Trip Dial: 28 → 40 A, 40A F.L.C, 40A Contact Rating, 22 kW 3P
- RS Stock No.:
- 875-1093
- Mfr. Part No.:
- 3RU2136-4FB0
- Manufacturer:
- Siemens
Subtotal (1 unit)*
MYR862.96
FREE delivery for orders over RM 150.00
In Stock
- Plus 4 unit(s) shipping from 16 November 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units | Per Unit |
|---|---|
| 1 + | MYR862.96 |
*price indicative
- RS Stock No.:
- 875-1093
- Mfr. Part No.:
- 3RU2136-4FB0
- Manufacturer:
- Siemens
Specifications
Technical data sheets
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | Siemens | |
| FLC Motor Rating | 40A | |
| Product Type | Thermal Overload Relay | |
| Relay Contact Current | 40A | |
| Series | SIRIUS 3RU2 | |
| Mount Type | Contactor | |
| Pole and Throw Configuration | 3P | |
| Power Rating | 22kW | |
| Terminal Type | Screw | |
| Normal State Configuration | 1 NO/1 NC | |
| Reset Method | Automatic & Manual | |
| IP Rating | IP20 | |
| Number of Auxiliary Contacts | 2 | |
| Width | 55mm | |
| Adjustable Current Range | 28 → 40 A | |
| Minimum Operating Temperature | -40°C | |
| Contact Voltage | 690V ac | |
| Maximum Operating Temperature | 70°C | |
| Depth | 105mm | |
| Standards/Approvals | UKCA, REACH, CCC, UL, EAC, IEC, WEEE (2012/19/EU), RoHS, CE | |
| Select all | ||
|---|---|---|
Brand Siemens | ||
FLC Motor Rating 40A | ||
Product Type Thermal Overload Relay | ||
Relay Contact Current 40A | ||
Series SIRIUS 3RU2 | ||
Mount Type Contactor | ||
Pole and Throw Configuration 3P | ||
Power Rating 22kW | ||
Terminal Type Screw | ||
Normal State Configuration 1 NO/1 NC | ||
Reset Method Automatic & Manual | ||
IP Rating IP20 | ||
Number of Auxiliary Contacts 2 | ||
Width 55mm | ||
Adjustable Current Range 28 → 40 A | ||
Minimum Operating Temperature -40°C | ||
Contact Voltage 690V ac | ||
Maximum Operating Temperature 70°C | ||
Depth 105mm | ||
Standards/Approvals UKCA, REACH, CCC, UL, EAC, IEC, WEEE (2012/19/EU), RoHS, CE | ||
- Switching Devices for Load Feeders
- Datasheet_3RU2136-4FB0
- Sirius Innovation Accessory Guide
- Sirius Innovation Catalogue
- Sirius Innovations Switching Devices
- Solutions for frequent switching or soft starting
- Basic Information
- Siemens Sirius Migration
- Environmental Product Declaration
- Instruction Sheet - 3RU2136-4FB0
RoHS Status: Exempt
- COO (Country of Origin):
- DE
Siemens SIRIUS 3RU2 Series Thermal Overload Relay, 28 to 40A Adjustable Current, 22kW Power - 3RU2136-4FB0
This thermal overload relay provides motor protection by monitoring and interrupting excessive motor current in three-phase systems. Designed for contactor mounting, it delivers thermal protection across an adjustable current range and supports both automatic and manual reset modes. The device operates at supply voltages up to 690 V ac and is suitable for installation where ambient temperatures range from −40 °C to +70 °C.
Features and Benefits:
• 28 to 40 A adjustable range offering precise motor protection
• 40 A operational current enabling up to 22 kW at 500 V
• Class 10 trip behaviour limiting motor thermal stress
• IP20 front protection with finger-safe touch prevention
• Screw terminals for main and auxiliary circuits allowing robust connections
• 40 A operational current enabling up to 22 kW at 500 V
• Class 10 trip behaviour limiting motor thermal stress
• IP20 front protection with finger-safe touch prevention
• Screw terminals for main and auxiliary circuits allowing robust connections
Applications
• Used with contactors in industrial motor control panels
• Suitable for three-phase motor protection up to 22 kW
• Ideal for retrofitting in existing control installations
• Can be used for requiring automatic/manual reset modes
• Suitable for three-phase motor protection up to 22 kW
• Ideal for retrofitting in existing control installations
• Can be used for requiring automatic/manual reset modes
What reset options does it provide?
It supports automatic and manual reset, with a typical recovery time of 10 min after an overload trip.
How many auxiliary contacts are available and what is their purpose?
It includes one NO contact for trip signalling and one NC contact for contactor disconnection.
What are the Terminal and conductor connection capabilities?
Main screw Terminals accept solid or stranded conductors up to 50 mm², or two conductors per Terminal where specified
auxiliary terminals accept up to 2.5 mm².
What short-circuit protection is required for the auxiliary circuit?
A 6 A protective device is required for the auxiliary switch where SCC ≤ 0.5 kA and U ≤ 260 V.
Note
Screw Terminals can only be used with screw Terminal overloads and spring Terminals can only be used with spring Terminal overloads.
Approvals
CE, UL, CSA
Related links
- Siemens Trip Dial: 34 → 40 A 40 A F.L.C 18.5
- Siemens Trip Dial: 47 → 57 A 57A Contact Rating 3P
- Siemens Trip Dial: 62 → 73 A 73A Contact Rating 3P
- Siemens Trip Dial: 18 → 25 A 3A Contact Rating, 22 kW 3
- Siemens Trip Dial: 28 → 40 A 3A Contact Rating, 690V 3
- Siemens Trip Dial: 10 → 25 A 3A Contact Rating 230V
- Siemens Trip Dial: 10 → 28 A 3A Contact Rating 230V
- Siemens Trip Dial: 20 → 25 A 3A Contact Rating 690V
