Interface Converter RS-232/RS422, RS-232/RS-485

From Phoneix Contacts, the DIN-Rail mounted PSM-ME-RS232/RS485-P Interface converter is designed to convert RS-232 interface signals bi-directionally to the RS-485 and RS-422 standard. The robust dual-channel converter is a category 3 device designed for installation in zone 2 potentially explosive areas. It meets the requirements of EN 60079-0:2012+A11:2013 and EN 60079-15:2010.

Featuring diagnostic and status indicator LEDs for supply voltage and RS232 data reception and transmission. The PSM-ME-RS232/RS485-P Interface converter offers the user the flexibility to meet the many demands of today’s industrial applications.

Programming

RS-422/RS485 standards to create fast interference-safe point-to-point connections between participants in industrial applications
For programming and parameterization connections, e.g. between PC and S5 PLC controls or drive regulators with RS-422/RS-485 interfaces

Features and Benefits

• RS-422 4-wire point-to-point operation
• RS-485 2-wire operation, half-duplex
• RS-485 4-wire operation, full-duplex
• Automatic RS-485 transmit/receive changeover
• Transmission speed of 4.8 kbps to 115.2 kbps
• Integrated data indicator for dynamic indication of transmit and receive data
• High-quality 3-way isolation between the power supply, RS-232, and RS-422/RS-485
• Integrated surge protection with transient discharge to the DIN rail

Application Examples

RS-232 to RS-485

The RS-485 standard is employed where more than two devices need to communicate with each other. By converting the RS-232 point-to-point interface to the bus-capable RS-485 standard, up to 32 devices may be networked via a 2-wire cable (semi-duplex) or 4-wire cable (full-duplex).

Possible applications:
· RS-232 master adjustment
· Programming/parameterization connection
· In networking RS-232 devices, the software must ensure devie addressability

RS-232 to RS-422

The RS-422 interface is an interface for point-to-point connections.

Possible applications:
· Interface adaptation to RS-422 devices
· Point-to-point connections of up to 1200 m; for range increase and interference-free transmission of RS-232 signals

Specifications
Attribute Value
Supply Voltage 24 V dc
Mounting Type DIN Rail
Minimum Operating Temperature 0°C
Maximum Operating Temperature +55°C
Operating Temperature Range 0 +55 °C
Series PSM-ME-RS232/RS485-P
1 Within 2 working day(s)
6 Within 4 working day(s) (Global stock)
Price Each
MYR 1,312.21
units
Per unit
1 +
MYR1,312.21
Related Products
Suitable for the EA-PS 3000B and EA-PS 9000 ...
Description:
Suitable for the EA-PS 3000B and EA-PS 9000 seriesEasy to install – Plug&PlayNo external power supply requiredSeparate settings for current and voltageActual values for current and voltage can be recorded separatelyStatus signals can be recorded separatelyControl signalsEvaluation and graphical display ...
Symmetric DIN rail mounting units with finger protected ...
Description:
Symmetric DIN rail mounting units with finger protected terminals designed for use in process control and instrumentation applications. Single or dual level trip amplifiers from a single Input.Each trip can be arranged so that the alarm condition can be above ...
Pluggable galvanic insulators to ensure reliable disconnection of ...
Description:
Pluggable galvanic insulators to ensure reliable disconnection of a signal and its associated electronic component.Signal input 0 (4) → 20 mA and output 0 (4) → 20 mA.Input and output circuits do not require an external power supply.The base consists ...
Converter: RS232 to RS485 / RS422Galvanically isolated up ...
Description:
Converter: RS232 to RS485 / RS422Galvanically isolated up to 1000 Vdc9-pin SUB-D connector for RS232 connection RJ11 connector or terminal strip for RS485 / RS422 connectionAutomatic RS485 send / receive control, no handshaking requiredHalf duplex (RS485) and full duplex (RS422)DTE ...