Eaton Overload Relay - 1NO/1NC, 3 A Contact Rating, 2 W, 24 → 240 V ac/dc

  • RS Stock No. 297-2395
  • Mfr. Part No. 066168 & EMT6-DBK
  • Manufacturer Eaton
Technical data sheets
Legislation and Compliance
RoHS Status: Not Applicable
Product Details

Klockner-Moeller EMT-6 Range

Provide protection to motors or other machines which require the temperature of their windings to be monitored and not exceeded, otherwise serious damage may occur

Features and Benefits:

a.c. or d.c. operating voltages
Rated current; 6A
DIN rail mounting
Can be screw mounted using adaptor (stock no. 296-2382)

Functions within the series:

All models have thermistor protection and auto reset

297-2351 EMT6 24-240 V AC/DC
297-2373 EMT6-DB 24-240 V AC/DC plus manual/remote reset and fault memory
297-2395 EMT6-DBK plus undervoltage protection and short-circuit monitoring
297-2367 EMT6 (230V) 230 V AC
297-2389 EMT6-DB (230V) 230 V AV plus manual/remote reset and fault memory

Applications:

Used for machine protection in automation, overload relays are often used in heavy-duty industrial settings, factory, motor, and electronic settings.

Specifications
Attribute Value
Control Voltage 24 → 240 V ac/dc
Contact Current Rating 3 A
Range EMT
Contact Voltage Rating 400 V ac
Mounting Style DIN Rail Mount
Series EMT6
Normal State Configuration NO/NC
Number Of Auxiliary Contacts 2
Power Rating 2 W
Terminal Type Screw
Reset Method Automatic, Manual
Depth 22.5mm
Length 102mm
Width 78mm
Maximum Operating Temperature +45°C
Minimum Operating Temperature -25°C
Operating Temperature Range -25 → +45 °C
10 In Global stock for delivery within 4 - 6 working days
Price Each
MYR 1,502.41
units
Per unit
1 - 5
MYR1,502.41
6 +
MYR1,456.76
Related Products
Mechanical ResetVertical mouting106 x 45 x 58mm (H ...
Description:
Mechanical ResetVertical mouting106 x 45 x 58mm (H x W x D)Ingress protection to IP65Overload relays only for the discontinued 4kW (AC3) D.O.L starter.
The Siemens SIRIUS series contactor relay has contactor ...
Description:
The Siemens SIRIUS series contactor relay has contactor size S00. It has auxiliary and control current circuit of screw type terminals. The design of fuse link is to protect from short circuit. Degree of pollution is 3Protection class IP20Operating temperature ...
Protects the motor against phase failure or overloadShort ...
Description:
Protects the motor against phase failure or overloadShort circuit protection when fitted directly to a contactSuitable for protection of Atex motorsSingle phase sensitivity to IEC/EN 60947When fitting overload relay remote from contactor or using more than one overload relay, use ...
These are for use with DILM contactors DILM40 ...
Description:
These are for use with DILM contactors DILM40 to DILM65. Fits below DILM 40 to DILM65 contactorsProvides short circuit protection for motorsWhen fitting overload relay remote from contactor, or using more than one overload relay, use remote mounting base (stock ...