PR Electronics 2 Channel Galvanic Barrier, Repeater power supply, Current, Voltage Input, Current, Voltage Output, ATEX
- RS Stock No.:
- 796-6954
- Mfr. Part No.:
- 5104BB
- Manufacturer:
- PR Electronics
17 In Global stock for delivery in 4-6 working days, delivery time may vary for certain locations or FTZ
Added
Price Each
MYR3,413.83
Units | Per Unit |
1 + | MYR3,413.83 |
- RS Stock No.:
- 796-6954
- Mfr. Part No.:
- 5104BB
- Manufacturer:
- PR Electronics
Legislation and Compliance
- COO (Country of Origin):
- DK
Product Details
5104B Type - Ex Repeater / Power Supply
The 5104B is a safety barrier for analog current / voltage signals for a hazardous area.
The repeater is based on microprocessor technology for gain and offset. The analog signal is transmitted at a response time of less than 25 ms.
The repeater is based on microprocessor technology for gain and offset. The analog signal is transmitted at a response time of less than 25 ms.
Features and Benefits
Ex Repeater and power supply
1:1 or signal conversion of analog current / voltage signals
1-channel version, 3-port 3.75 kVac galvanic isolation (stock-no. 796-7004)
2-channel version, 5-port 3.75 kVac galvanic isolation (stock-no. 796-6954)
Supply voltage and safety barrier for 2-wire transmitters
Loop supply > 17.1 V in hazardous area
20 programmable measurement ranges
Inputs, outputs, and supply are floating and galvanically separated
The output can be connected either as an active current /voltage transmitter or as a 2-wire transmitter
Universal supply by AC or DC
For mounting in a hazardous area
DIN rail mounting
1:1 or signal conversion of analog current / voltage signals
1-channel version, 3-port 3.75 kVac galvanic isolation (stock-no. 796-7004)
2-channel version, 5-port 3.75 kVac galvanic isolation (stock-no. 796-6954)
Supply voltage and safety barrier for 2-wire transmitters
Loop supply > 17.1 V in hazardous area
20 programmable measurement ranges
Inputs, outputs, and supply are floating and galvanically separated
The output can be connected either as an active current /voltage transmitter or as a 2-wire transmitter
Universal supply by AC or DC
For mounting in a hazardous area
DIN rail mounting
Note
Not suitable for new installations requiring certification to the latest ATEX standards - see ATEX certificate DEMKO 99ATEX127186 and EU Declaration of Conformity for details
PR Electronics - Ex Interfaces
Specifications
Attribute | Value |
---|---|
Number of Channels | 2 |
Module Type | Repeater power supply |
Barrier Type | Galvanic Barrier |
Output Signal Type | Current, Voltage |
Maximum Voltage | 250V ac |
Hazardous Area Certification | ATEX |
Input Signal Type | Current, Voltage |
Maximum Operating Temperature | +60°C |
Minimum Operating Temperature | -20°C |
Supply Voltage | 19.2 → 300 V dc, 21.6 → 253V ac |
Safety Current Maximum | 400mA |
Safety Voltage Maximum | 250 V ac |
Series | 5100 |
Operating Temperature Range | -20 → +60°C |