Lapp Olflex Classic 110 CY 4 Core CY Control Cable 2.5 mm², 50m, Screened

  • RS Stock No. 812-4558
  • Mfr. Part No. 1135404
  • Manufacturer Lapp
Technical data sheets
Legislation and Compliance
RoHS Certificate of Compliance
COO (Country of Origin): DE
Product Details

Ölflex® Classic 100CY

ÖLFLEX® Classic 100 CY cables are a screened connecting and control cable for flexible use and fixed installation for medium mechanical use. They are for use in dry, damp and wet rooms. They can only be installed outdoors with UV protection and in observation of the temperature range. At room temperature, it is resistant against acids, caustics solutions and certain oils. ÖLFLEX® Classic 100 CY cables are used as supply and interconnecting cable for controlling machine tools, production lines, control equipment on conveyors. ÖLFLEX® 100 CY cables can also be used in measuring regulating and computer units. The screen is a protection against electrical interference

Features and Benefits

• Design: in accordance to HD 21.13S1 that is VDE 0281-13
• Conductor: bare copper, fine wire strand in accordance to IEC 60 228 that is VDE 0295, class 5
• Core insulation: LAPP special PVC compound P8/1, better than the PVC compound TI2 in accordance to VDE 0207 part 4
• Identification: up to 5 cores are colour coded in accordance to HD 186 resp. VDE 0293, with green/yellow ground conductor
• Inner sheath: PVC compound TM2 in accordance to VDE 0281-1
• Screen: Braid of tinned copper, coverage 85%. Transfer impedance in accordance to HD21.13 S1 250mΩ/m at 30 MHz
• Outer sheath: PVC compound TM2 in accordance to VDE 0207 part with increased request to LAPP specification
• Minimum bending radius: flexible use 20 x cable diameter; fixed use 6 x cable diameter
• Flame retardant: in accordance to IEC 60 332.1
• Tests: in accordance to IEC 60 811 resp. VDE 0472 and VDE 0473
• EC directive: This cable confirms to ECD 73/23/EEC (low voltage directive)

Standards

This cable confirms to ECD 73/23/EEC (low voltage directive).

Specifications
Attribute Value
Number of Cores 4
Cross Sectional Area 2.5 mm²
Length 50m
Current Rating 26 A
Outer Diameter 11.3mm
Voltage Rating 300/500 V
Sheath Colour Transparent
American Wire Gauge 13 AWG
Earth Cable Yes
Minimum Operating Temperature -40°C
Maximum Operating Temperature +80°C
Sheath Material Polyvinyl Chloride PVC
Bedding Material PVC
Conductor Resistance 7.98 Ω/km
Screened/Unscreened Screened
Insulation Material PVC
Screen Type Tinned Copper Braid
Core Strands 50/0.25 mm
Filler Material Non-Wicking Filler
Minimum Bend Radius Fixed - 6 x D Occasional Flexing - 20 x D
Conductor Material Copper
Series ÖLFLEX CLASSIC 110 CY
4 In Global stock for delivery within 4 - 6 working days
Price 1 Reel of 50 Metre(s)
MYR 1,289.59
Reel(s)
Per Reel
Per Metre*
1 +
MYR1,289.59
MYR25.792
*price indicative
Related Products
From Lapp, this Olflex Robust series cable has ...
Description:
From Lapp, this Olflex Robust series cable has excellent environmental resistance and is ideal for use in food production industries. It also features copper screening, and is EMC compliant for use in environments where electromagnetic interference might be an issue.This ...
From Lapp, this Spirex Data cable is a ...
Description:
From Lapp, this Spirex Data cable is a data and control cable with a spiral construction that offers greater flexibility. The coiled cable is abrasion resistant, and can extend up to four times its closed spiral length, resulting in a ...
Shielded computer cables with fine-wire flexible cord made ...
Description:
Shielded computer cables with fine-wire flexible cord made of plain Cu wiresStranded in pairs (TP) with pair shielding through Cu covering and PVC pair-sheathingPairs shielded togetherPlastic film coveringTotal shield braid made of tin-plated Cu wiresCore colours in acc. with DIN ...
EMC-optimised motor cable, low-capacitance and double screened for ...
Description:
EMC-optimised motor cable, low-capacitance and double screened for very large power drive systems. • 3+3 symmetry reduces common-mode interference effects• Allows EN 61800-3-compliant, EMC-compliant installation of power drive systems• Flame-retardant according to IEC 60332.1.2.